This paper proposes an improved method to enhance the dc response of a frequency-dependent transmission line model used in EMT studies. A modification to the rational function approximation of propagation and characteristic admittance matrices of a transmission line is introduced to enforce exact dc values at 0 Hz. Furthermore, weighting factors are applied to improve accuracy at low frequencies. Finally, the order of the propagation function is reduced to decrease the computational effort.The validity of the proposed approach is demonstrated using examples involving underground cables and overhead lines. First, the effect of dc correction is demonstrated by comparing transmission line frequency domain characteristics. In addition, time domain simulations via open and short circuit conditions show a more accurate simulation of HVDC transmission lines with the proposed method.