Abstract

This paper proposes a simple but effective method based on shunt passive filters to enforce passivity on a frequency dependent transmission line model for multi-conductor cables and overhead lines. The passivity enforcement algorithm is applied to a widely-used frequency dependent line model in EMT-type software, the Universal Line Model. The passivity violating regions of the transmission line model are identified using the frequency sweep method. The passive shunt series RLC filters are added to the nodes of the transmission lines to eliminate passivity violations. Examples of multi-conductor underground cable systems are presented to demonstrate the validity of the proposed approach.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.