Abstract

The detection and localization of partial discharge (PD) in air-insulated substations by ultra-high frequency (UHF) technology is widely studied. Existing UHF PD localization system mainly focus on time-difference of UHF signal, which requires very high synchronized sampling rate. This paper proposes a received signal strength (RSS) based angle of arrival (AoA) method by a circle UHF wireless sensor array. An AoA estimation scheme is derived through the radiation pattern of designed UHF antenna. Interpolation and neural network are applied to improve the AOA resolution. A field test is performed to verify the effectiveness of the proposed PD localization system. The results show that the estimated error on average is below 7°. Compared to the time-difference-based method, the accuracy of our designed system is more feasible for practical application considering its significant low-cost feature.

Full Text
Published version (Free)