Abstract

The quick detection and localization of partial discharge (PD) in an air-insulated substation (AIS) based on ultrahigh-frequency (UHF) sensor arrays are efficient for power equipment monitoring. The adopted UHF PD time difference of arrival (TDOA) methods mainly use the time difference of electromagnetic wave signals. Thus, the system requires both a high sampling rate and time synchronization accuracy, leading to a high cost and large size. In this study, the feasibility and accuracy of PD DOA in an AIS were investigated using a UHF wireless sensor array and the received signal strength indicator. First, the power pattern of the designed UHF wireless sensor array was obtained via an offline experiment. Then, a statistical approach to the PD DOA method based on the maximum likelihood estimator was employed to obtain the preliminary DOA result. Finally, interpolation and clustering algorithms were used to improve the accuracy of the DOA. A laboratory test was conducted. The average error of the PD DOA was less than 6{\deg}, and the cost-effectiveness and portability were clearly improved.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.