Abstract
Ultra-high-frequency (UHF) method has been applied to detect and localize partial discharge (PD) in air-insulated substation (AIS). The localization accuracy is closely dependent on the configuration of antenna array. This paper presents a PD localization error simulation method. Assuming that the estimated time difference of arrival (TDOA) error is normally distributed, the mean value and standard derivation of localization error for numerous positions in AIS are calculated with a Monte Carlo method. Then the localization error of square, Y shape, triangle and diamond arrays are compared, and the factors influence the localization error are analyzed. Since the optimal orientation is easily to be recognized and with minor distance error, the diamond array is more suitable for PD localization in AIS. Experiments are conducted for square and diamond arrays to calculate the localization error, and confirm the effectiveness of proposed simulation method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.