Abstract

This paper aims to propose testing methods and standards for evaluating refrigerant recovery and recycling equipment so that the methodology can be used for alternative material-related technological research in South Korea. To achieve this, the paper establishes test methods based on international and domestic standards. Major test items can be classified into following categories; equipment performance and the quality of recycled refrigerant. Selected refrigerants are HCFC-22, HCFC-123 and HFC-134a. The resulted equipment performance revealed that the movable type, which is the majority model in South Korea, has recovery and capacity advantages to be suited into international standard. On the other hand, the quality of recycled refrigerant lagged in purity and high-boiling residue. The purity of HCFC-22 was 99.3% which was obviously contaminated than the pure refrigerant and the international standard. High-boiling residue of HCFC-22 and HCFC-123 also showed lower numerical value compared to the international standard. Aforementioned results imply the gap between international and domestic standard. Based on result values of test equipment and precedent studies, approximate standard performance criteria and values were set as proposed by South Korean standard.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.