Abstract

It is well-known that adding a notch filter in series with the typically employed type-II (or PI) regulator allows improving the tradeoff between dc-link voltage dynamics and grid-side current total harmonic distortion (THD) in practical single-phase power factor correction rectifiers. The article demonstrates that notch filter utilization alternatively allows reducing the value of dc-link capacitance in case hold-up time requirement is absent. The revealed value of minimum capacitance is expressed by explicit function of possible mains frequency values range, maximum expected grid voltage magnitude, rated system power, dc-link voltage set point, maximum tolerable grid-side current THD, and the desired phase margin (PM) of dc-link voltage loop. It is demonstrated that the proposed approach yields fourfold reduction of dc-link capacitance for typical values of 5% tolerable grid-side current THD under 40° PM constraint. Experimental results exhibit close-fitting resemblance to corresponding analytical predictions, verifying the proposed methodology.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.