Abstract

Modular multilevel converter (MMC) shows prominent advantages on supplying passive networks, which are usually classified by power supply shortage and relatively weak structure. In order to reduce the unnecessary outage time and improve the system stability, an adaptive ac auto-reclosing scheme for passive networks is proposed based on characteristic signal injection. Additional MMC controller is designed to inject the characteristic signals into the healthy line, which in turn induces corresponding signals to the faulty line. Then fault properties are assessed by the travelling wave based fault location method. Finally, an adaptive auto-reclosing scheme is proposed to shorten the reclosing time and avoid the second fault shock to a large extent. The proposed scheme could be applied for both single-circuit and multi-circuit transmission lines. The simulation results obtained from PSCAD/EMTDC verify the effectiveness of the proposed method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.