Locating fault position in a series compensated transmission line is a difficult task due to the non-linear characteristics of the metal-oxide varistor which is present in the protection system of the compensator. In this paper, a model-free two-terminal traveling wave-based fault location method for a series compensated line is proposed. The technique makes use of two subroutines which calculate the fault locations assuming that the fault position to be on the left and right side of the series compensator respectively. The method then selects the correct fault location of the two by a special logic based on faulted half-section identification. The first two traveling wave arrival times recorded at both the terminals of the line are used in the method. The proposed technique does not require model information of the series capacitor and transmission line. It has been verified using the PSCAD/EMTDC model of a 400-kV, 300 km transmission line which is compensated by a fixed series capacitor in the middle and line ends. The performance of the proposed method is compared with a commercially available classical two-ended techniques and setting-free method.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.