This study addresses the load frequency control (LFC) within a multiarea power system characterized by diverse generation sources across three distinct power system areas. area 1 comprises thermal, geothermal, and electric vehicle (EV) generation with superconducting magnetic energy storage (SMES) support; area 2 encompasses thermal and EV generation; and area 3 includes hydro, gas, and EV generation. The objective is to minimize the area control error (ACE) under various scenarios, including parameter variations and random load changes, using different control strategies: proportional-integral-derivative (PID), two-degree-of-freedom PID (PID-2DF), fractional-order PID (FOPID), fractional-order integral (FOPID-FOI), and fractional-order integral and derivative (FOPID-FOID) controllers. The result analysis under various conditions (normal, random, and parameter variations) evidences the superior performance of the FOPID-FOID control scheme over the others in terms of time-domain specifications like oscillations and settling time. The FOPID-FOID control scheme provides advantages like adaptability/flexibility to system parameter changes and better response time for the current power system. This research is novel because it shows that the FOPID-FOID is an excellent control scheme that can integrate these diverse/renewable sources with modern systems.
Read full abstract