Solar energy integrated with the building is an important approach for the synchronous development of solar energy and architecture. The energy gain of the solar collector integrated with the pitched roof has been greatly influenced by the roof azimuth and tilted angle. Investment cost of the collectors is mainly decided by the size of the collector area. Accordingly, it is significant for solar building design to economically determinate the area compensation of the solar collector at different azimuth and tilted angles. Take Kunming and Beijing as examples, area compensation for the flat-plate tube-fin solar collector used in southern regions and the evacuated tube collector with cylindrical absorbers used in northern regions in China have been theoretically calculated. The results to some extent show that the daily horizontal solar radiation, ambient temperature, the azimuth and tilted angle of the collector integrated into the roof have an influence on the area compensation. The azimuth angle and tilted angle of the roof are the main factors that influence the A/ A 0, which is defined as the collector area ratio of the non-south-facing collectors to the south-facing ones with the optimal tilted angle. Comparative studies found that the range of A/ A 0 for the evacuated tube collector used in the northern regions is close to that for the flat-plate tube-fin solar collector used in the southern regions. When the pitched roof tilted angle β ∈ [25°, 45°] and the azimuth angle ∣ γ∣ ⩽ 30°, the collectors can intercept a lot of solar radiant-energy. Considering the economic situations of the ordinary consumers in China, the optimal area compensation A/ A 0 ⩽ 1.30 is recommended in this paper.