Abstract The Energy Efficiency in Industrial, Commercial, and Public Sector (EINCOPS) program is the result of a collaboration between the Indonesian Ministry of Energy and Mineral Resources and Danida (Danish International Development Assistance), which began in 2008 to support Indonesian government policies in achieving development goals in the field of sustainable environmental management. Energy users have gradually adopted energy efficiency measures in the industrial, commercial, and public sectors, starting with a large class. This research aims to obtain the optimal temperature range for using a chiller machine so that it continues to run efficiently. The method used is to calculate the coefficient of performance and energy efficiency ratio of each chiller when it is used. The number of chillers can be affected by the temperature range of the air handling unit (AHU), which uses wind from the environment as the main source for processing, and the temperature range is linear with weather conditions. This research found that in the environmental temperature range of 26°–29° Celsius taken by AHU for distribution to production areas, chiller performance is still not optimal. In the previous operation, three chillers were used out of the four available units, so after knowing the results of the chiller load analysis in this temperature range were still below standard or not optimal, the number of chillers could be reduced from three units full time to only two units when the temperature environment was in the range of 26°–29° Celsius. The results of calculating the average Coefficient of Performance and Efficiency Energy Ratio using two chillers when the temperature range of 26°–29° Celsius is still included in the standard, namely by increasing 0.15, the pre-improvement value is 5,833, and the chiller efficiency load increases to 14 percent.