Abstract In this paper which was performed to bring public attention t o the need for developing an photoelectric smoke detector that detects smokes emitted from d iverse fire sources, it was confirmed that the photoelectric smoke detector may not respond to certai n smoke types depending on the size and color of smoke particles. The test was performed on a photo electric smoke detector which is being used generally for specific fire targets specified in UL268, in cluding paper fire, wood fire and flammable liquid fire, while the actual response performance of the fire detector, as well as respective smoke particles collected from different fire source which were photographed with a SEM(Scanning electron microscope) were analyzed in the test for this study. keywords: photoelectric smoke detectors, paper fire, wood fire, flammable liquid fire 1. 서 론 화재감지기는 화재 시 발생하는 열, 연기, 불꽃 또는 연소생성물을 자동적으로 감지하여 자동화재탐지설비의 수신기에 신호를 보내어 경보장치를 작동하게 하는 장치로 화재초기에 거주자 및 관계자의 빠른 대피 및 신속한 소화활동을 도모하도록 유도하는 역할을 하기에 중요시되고 있다[1],[2],[3]. 이런 화재감지기는 감지대상에 따라 크게 열감지기, 연기감지기, 불꽃감지기로 구분되어 지는데 이 중 연기감지기가 화재초기에 발생되는 연기를 빠르게 감지하기 때문에 일반적으로 사용되어지고 있다.[4],[5] 이렇게 일반적으로 사용되어지는 연기감지기는 작동방식에 따라 이온화식과 광전식(이하 “산란광식”이라 한다)으로 작동하는 방으로 분류되어지는데, 이온화식 연기감지기의 경우 불꽃을 수반하는 화원으로부터 발생된 연기에 대하여 응답특성이 산란광식으로 작동하는 연기감지기 보다 우수하다는 특징이 있고, 산란광식 연기감지기의 경우 불꽃을 수반하지 않는 화원으로 부터 발생된 연기에 대하여 이온화식 연기감지기보다 우수한 특징을 가지고 있다[6],[7]. 이에 각 연기감지기는 화재발생시 나타나는 응답특성에 따라 특정소방대상물에 적절히 설치되어 사용되어 왔지만, 최근 이온화식 연기감지기의 이온화 챔버 내부에 방사성 동위원소인 Am 241(아메리슘 241)의 위험성으로 인한 생산 중단으로 현재는 하나의 광센서로 연기를 감지하는 산란광식 연기감지기만 개발 및 보급되고 있다.†Corresponding Author : Jong Hwa Lee, Gwangju Gwangsan-gu Seobong-dong Honam University, E-mail: buldori@honam.ac.kr Received January 15, 2016; Revision Received March 02 , 2016 ; Accepted March 21, 2016.