The detection of corona-related defects in transmission lines has been included in the work of transmission line defect detection. Ultraviolet detection technology has gradually been widely applied in the field of corona discharge detection. However, the current research on the application of ultraviolet detection technology in transmission lines is relatively simple and mainly limited to using changes in the photon count to determine whether corona discharge has occurred. To address this, this study used a mini corona cage to simulate transmission lines and measured the changes in the photon count, spot area, and corona current in the corona inception process of different types of smooth, stainless-steel conductors. This study also investigated the variations in the photon count and spot area depending on conductor corona intensity, ultraviolet imager gain, and observation distance. The results show that the photon count and spot area can, to some extent, reflect the intensity of corona discharge. Both the photon count and spot area exhibited quadratic relationships with the voltage. As the observation distance increased, both the photon count and spot area showed exponential decay. The photon count exhibited a trend of initially increasing, then decreasing, and finally increasing again with the increase of gain, while the spot area showed exponential growth with increasing gain. The photon count and spot area can complement each other to identify and characterize the intensity of corona discharge.