In the last two decades, HTS cables have been successfully demonstrated around the world, preparing HTS power cables for a full commercial introduction. Among the demonstration projects, circulating subcooled liquid nitrogen to maintain the HTS cable at operating temperature is a widely adopted approach. In this approach, the cooling systems are absolutely critical to the successful operation of the HTS cables. This paper describes the progress and status of the cryogenic refrigeration system designed and manufactured for project Hydra, which is a project jointly funded by the U.S. Department of Homeland Security Science and Technology Directorate, American Superconductor and Consolidated Edison Company of New York, Inc. American Superconductor is leading the team supported by Con Edison, Ultera, Altran Solutions, and DH Industries. The cable is an inherently fault current limiting HTS cable, approximately 200 m long and designed to carry 96 MVA at a distribution level voltage of 13.8 kV. The cable will be installed and energized near New York City. The refrigeration system was designed and manufactured by DH Industries. This paper provides details on the successful factory acceptance testing completed in November 2014.