The development of high-rise buildings worldwide has given rise to significant concerns regarding their excessive electricity consumption. Among the various categories of high-rise structures, hotels used for business and conferences stand out as particularly extravagant in their energy use. The consequence arising from excessive energy usage is an escalation in carbon emissions, which is a primary driver of global warming. Therefore, this study aims to investigate the energy use intensity (EUI) of a hotel building located in Jakarta, Indonesia. In order to improve energy performance, this study explored various options for renovating the building envelope, such as incorporating insulation and a roof covering, as well as implementing building-integrated photovoltaics (BIPV). The building envelope renovations demonstrated a notable reduction in energy use by 15.8–27.7% per year. BIPV, such as curtain walls and double-skin façades, generated an energy use reduction of 4.8–8.6% per year. Remarkably, by combining the two approaches (i.e., adding insulation and a roof covering in the building envelope and adopting BIPV as double-skin façades), the potential reduction in energy use reached up to 32.2% per year. The findings can assist decision-makers in developing building renovation strategies for high-rise buildings while considering energy conservation.