Accurate ventilation control is crucial for maintaining a healthy and productive environment in research-specialized pig facilities. This study aimed to evaluate actual ventilation rates and ventilation efficiency by investigating different inlet and exhaust configurations. The research was conducted in two pig rooms, namely pig room A and pig room B, in the absence of animals and workers to focus solely on evaluating the ventilation system's performance. Actual ventilation rates were measured using hood-type anemometers, and the local air change per hour was analyzed at various measurement points via tracer gas decay experiments. The results demonstrated that specific inlet and exhaust combinations, such as side inlet/chimney outlet and ceiling inlet/side outlet, exhibited higher ventilation rates. However, the measured ventilation rates were much lower than the manufacturer's specifications. The side exhaust fan closer to the pig activity space demonstrated better ventilation effectiveness for the animals than the chimney exhaust fan. Additionally, the ceiling inlet exhibited superior air distribution and uniformity. Lower ventilation rates and higher infiltration ratios resulted in reduced ventilation efficiency, with the difference between pig and worker activity spaces being pronounced. This study emphasizes the importance of selecting optimal inlet and exhaust configurations to achieve efficient ventilation and create a healthy environment for both pigs and workers.