Abstract

The switching off and on of small capacitive currents charging busbar capacitances, connection conductors and open circuit-breakers with disconnectors causes high-frequency transients in high-voltage networks. In low voltage circuits, these transient processes induce dangerous overvoltages for the electronic equipment in the substation. A modified construction of the disconnector with a damping resistor was investigated. Digital simulation of the transient process in a high-voltage network during the arcing period between the disconnector contacts with and without damping resistor were performed. A significant decrease of the arcing duration and the decrease of the electromagnetic field magnitude in the vicinity of the operating disconnector were noticed. In the low-voltage circuit protected with the surge arrester, the overvoltage magnitude was not affected by the damping resistor due to the arrester protection effect.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.