The switching off and on of small capacitive currents charging busbar capacitances, connection conductors and open circuit-breakers with disconnectors causes high-frequency transients in high-voltage networks. In low voltage circuits, these transient processes induce dangerous overvoltages for the electronic equipment in the substation. A modified construction of the disconnector with a damping resistor was investigated. Digital simulation of the transient process in a high-voltage network during the arcing period between the disconnector contacts with and without damping resistor were performed. A significant decrease of the arcing duration and the decrease of the electromagnetic field magnitude in the vicinity of the operating disconnector were noticed. In the low-voltage circuit protected with the surge arrester, the overvoltage magnitude was not affected by the damping resistor due to the arrester protection effect.