Abstract

In the present study, the effect of operational and geometrical parameters on the thermal effectiveness of shell and helically coiled tube heat exchangers was investigated. Analysis was performed for the steady state. The working fluid of both sides is water, that its viscosity and thermal conductivity were assumed to be dependent on temperature. Based on the results, two correlations have been developed to predict the thermal effectiveness, for wide ranges of mass flow rates ratio, dimensionless geometrical parameters and product of Reynolds numbers. Furthermore, it was found for same values of NTU and Cr, the effectiveness is averagely 12.6% less than the effectiveness of parallel flow heat exchangers and this difference is approximately constant.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.