Abstract

The construction of the Industrial Engineering Department building is an effort to support the educational infrastructure at Andalas University. However, the building construction process was stopped because the contractor had terminated the contract (breach of contract) and it took a long time to continue the construction. Before that, a structural evaluation of the building structure should be conducted due to the update of the building standards. In this study, the structural evaluation was carried out by analyzing and modelling the building using ETABS v.18 software, as well as loading analysis on the building regarding current Indonesian building standards such as SNI 1726-2019 for earthquake resistance building design, SNI 2847-2019 for requirements of the structural concrete building and SNI 1727-2020 for building minimum design loads. The results of the analysis show that several structural beams did not have a strong enough capacity to withstand the working loads, where the ultimate moment and shear values due to the influence of acting loads were more than the nominal moments and shear values. Retrofitting of the weak structural beams using the CFRP wrapping method was recommended to improve the structural capacity of the building.