Abstract

Experiment and numerical simulation were performed to research the possibility of adopting different ventilation modes for smoke confinement in a subway station fire accident. Bench scale experiments were conducted in a 1:50 scale model of a subway station. Fire Dynamics Simulator software (FDS) was utilized to carry out numerical simulations, which conducted in a full scale subway station. Experiment result agreed well with simulation result and the research showed that the different ventilation mode had different efficacy of smoke confinement released by the fire in basement 2. In addition, when the USME ventilation mode was adopted and there were smoke exhausted from basement 2 and air supplied into the basement 1, the efficacy of smoke confinement was the best. According to these cases conducted in this paper, the layouts of the ventilation vents had little influence on the efficacy of smoke confinement. Once the HRR was too big, the concentration would pass 50PPM and the amount of exhausted smoke should be increased.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.