Abstract

Transient characteristic analysis of inter-turn short circuit fault has been done which is paramount for detecting the earlier fault of dry-type air-core reactor. Dynamic physical process of inter-turn short circuit is theoretically analyzed for dry-type air-core reactor from normal running condition to inter-turn short circuit fault condition. Using ANSYS Maxwell, transient field circuit coupling calculation model is set up and the transient characteristic of inter-turn short circuit fault is simulated, which is also verified by experiments. The study shows that the short circuit ring causes a sudden change of magnetic field at the position of short circuit which can be detected by the detecting coils installed on the package of reactor. Inter-turn short circuit fault can be detected in the earlier fault period by the method proposed in this paper.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.