Abstract

Transient characteristic analysis of inter-turn short circuit fault has been done which is paramount for detecting the earlier fault of dry-type air-core reactor. Dynamic physical process of inter-turn short circuit is theoretically analyzed for dry-type air-core reactor from normal running condition to inter-turn short circuit fault condition. Using ANSYS Maxwell, transient field circuit coupling calculation model is set up and the transient characteristic of inter-turn short circuit fault is simulated, which is also verified by experiments. The study shows that the short circuit ring causes a sudden change of magnetic field at the position of short circuit which can be detected by the detecting coils installed on the package of reactor. Inter-turn short circuit fault can be detected in the earlier fault period by the method proposed in this paper.