Abstract

<para xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> A new approach is proposed to solve the directional overcurrent relay coordination problem, which arises from installing distributed generation (DG) in looped power delivery systems (PDS). This approach involves the implementation of a fault current limiter (FCL) to locally limit the DG fault current, and thus restore the original relay coordination. The proposed restoration approach is carried out without altering the original relay settings or disconnecting DGs from PDSs during fault. Therefore, it is applicable to both the current practice of disconnecting DGs from PDSs, and the emergent trend of keeping DGs in PDSs during fault. The process of selecting FCL impedance type (inductive or resistive) and its minimum value is illustrated. Three scenarios are discussed: no DG, the implementation of DG with FCL and without FCL. Various simulations are carried out for both single- and multi-DG existence, and different DG and fault locations. The obtained results are reported and discussed. </para>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.