Abstract

Introducing Distributed Generation (DG) into Power Delivery Systems (PDSs) alters protection design of these networks. Commonly approach to overcome this problem is disconnecting DG units from PDS during fault. In case of asynchronous DG type, because of installing shunt capacitive compensators, using FCL for restoration of relay coordination is not useful in some cases. In this paper, a new approach for restoration of directional over-current relay coordination using three type of Fault Current Limiter (FCL) is presented. The proposed restoration approach is carried out without altering the original relay settings or disconnecting DGs from PDSs during fault. The process of selecting FCL impedance type (inductive or resistive) and its minimum value is illustrated. Two scenarios are discussed: no compensator and whit compensator. Various simulations are carried out for both single and multi-DG existence, different DG and fault locations. The application of this approach is implemented into an IEEE typical distributed network and the obtained results are reported and discussed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.