Abstract
The anticipated high penetrations of small-scale embedded generators (SSEGs) on public low-voltage (LV) distribution networks are likely to present distribution network operators (DNOs) with a number of technical impacts relating to power quality, distribution system efficiency and potential equipment overloads. Impact studies need to be performed using suitable case study networks in order to evaluate the effects of SSEGs on LV distribution networks and quantify allowable SSEG penetration levels. The aim is to propose a methodology for predicting the technical impacts of SSEGs on LV networks without the need for developing a detailed computer-based model of the power system and simulating a range of operating scenarios. This methodology is drawn from an analysis of the key electrical characteristics that determine the response of LV networks to the addition of SSEGs, focusing on the following technical aspects: (i) voltage regulation, (ii) voltage rise, (iii) voltage unbalance, (iv) cable and transformer thermal limits and (v) network losses. The analysis is carried out on a UK generic and a European generic LV network and simulation results for both networks are presented and discussed. The proposed methodology is then applied to an existing public UK LV network operated by E.ON UK Central Networks, indicating a good agreement between predicted and simulation results.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.