Abstract

The paper presents the results of research in lightning surge waves and switching overvoltages transferred from a network of 220 kV to the 15.65 kV level of the step-up transformer in HPP 'Bajina Bašta'. Analysis of survey results lead to conclusion that transferred overvoltages can endanger 15.65 kV transformer windings and stator winding insulation. It was therefore suggested for the protection of the 15.65 kV isolation to install metal oxide surge arresters at a suitable place between the power generator bus bars and earthing.

Highlights

  • The paper presents the results of research in lightning surge waves

  • switching overvoltages transferred from a network of 220 kV

  • Analysis of survey results lead to conclusion that transferred overvoltages can endanger

Read more

Summary

Introduction

Maksimalne vrednosti prenetih napona na izolaciji [15,65] kV namotaja blok transformatora 242kV/15,65kV i izolaciji namotaja statora generatora dati su u tabelama 1 i 2 u procentima primenjene akcije prema izrazu: Akcija U1U1V oblika 1,3/57 μs/μs (sečen talas, ordinata levo) na 242 kV priključcima 1U i 1V i preneti naponi U2U, U2V i U2W (ordinata desno) na [15,65] kV strani blok transformatora 242kV/15.65kV kada je priključen generator (šema kada je blok na mreži)

Results
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.