This article discusses the performance problems associated with process water pumps. It highlights that at a boiler steam load in the 25% to 40% range, an automatic recirculation (ARC) valve is simply not accurate enough to detect a minimum pressure differential change of possibly 1–2 psig when the boiler drum level control valve closes for short-duration process demand changes. Converting the ARC valve to an electronic controller does not work reliably either. The amperage change is difficult to discern at low feedwater flow rates. Failure of the valve to open is a recipe for pump cavitation and becoming “steam bound.” If the boiler trips on “low water,” plant production can be affected immediately. For larger boilers with high-capacity, high-horsepower feed pumps, the ARC valve often becomes an energy conservation (cost) issue.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.