Abstract

Vacuum interrupters have been recognized as one of the most important sources of switching over-voltages in MV networks, leading to voltage escalation. These over-voltages are usually observed as a result of inductive current interruption which may accompany with multiple re-ignitions. Single phase fault current in high inductance-earthed networks is inherently inductive and therefore prone to cause dangerous over-voltages during interruption. To mitigate this problem, a resistor is usually inserted between ground and inductor neutral. In this paper, sizing of this resistor is investigated for an industrial plant. Also, prominent conditions affected by resistance value, leading to re-ignitions are studied. Firstly, resistor is sized through relevant IEEE recommendation. Then vacuum circuit breaker is efficiently modeled and using a new simulation-based method in PSCAD/EMTDC platform, the maximum over voltage figures are obtained for variety of operating points. Finally, simulation results are compared with those given by IEEE criterion and appropriate value for neutral resistance will be effectively determined.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call