Abstract

In this investigation, a mathematical model was developed to study the performance of cross-flow liquid desiccant air dehumidifier (LDAD). The results show that desiccant solution to air mass ratio has the greatest impact on performance of dehumidifier. Inlet air humidity ratio and temperature have significant influence on outlet air humidity ratio and temperature, respectively. The outlet air humidity ratio, outlet air temperature and outlet desiccant solution temperature are increased with inlet desiccant solution temperature increasing. The increase of solution fraction leads to a slight decrease in outlet humidity ratio and dehumidification rate, but a little increase in outlet air temperature. In addition, when the solution fraction is 48%, the outlet solution temperature reaches the maximum value. Numerical results are verified by experimental ones with a maximum deviation of 8.7% in the outlet air humidity ratio.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.