Abstract

The existing interphase fault auto-reclosure of distribution network has the risk of reclosing in permanent faults, it is necessary to identify the fault nature before three-phase reclosing. By using the more abundant electrical information after the injection of external voltage source, the varied characteristics of phase differences between voltage and current of interphase faults under different fault natures are analyzed for the 10kV distribution lines with shunt capacitors. The analysis shows that the circuit structure changes after the transient fault disappeared, and the phase difference between voltage and current becomes 90°, while the permanent fault circuit is stable with a phase difference of 120°. Therefore, using the phase differences between voltage and current before and after the fault disappearance, build a fault nature identification scheme. The results of simulation show that the proposed method can accurately identify the fault nature and is basically not affected by fault location and transition resistance which has good adaptability.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.