Abstract

Subsynchronous resonance (SSR) is a potential problem in power systems having series compensated transmission lines. Flexible AC transmission systems (FACTS) controllers are widely applied to mitigate subsynchronous oscillations (SSO). With the advent of wide area measurement (WAM) technology, it is possible to measure the states of a large interconnected power system with synchronized phasor measurement units (PMU). In this paper the concept of using remote signals acquired through PMU has been proposed to damp SSR. An auxiliary subsynchronous damping controller (SSDC) for a static VAr compensator (SVC) using the remote generator speed as the stabilizing signal has been designed to damp subsynchronous oscillations. The IEEE first benchmark model is used to show the effectiveness of the controller. Extensive simulation results in EMTDC/PSCAD show that an SVC already installed in a transmission system with the primary objective of improving power transfer capability can also damp SSR with the auxiliary controller using remote generator speed. Finally, the effect of signal transmission delay is discussed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.