This paper proposes a new auxiliary Subsynchronous Damping Controller (SSDC) for the Static Var Compensator (SVC) to damp out subsynchronous oscillations in power system containing series compensated transmission lines. The arrival of Wide Area Measurement (WAM) technology has made it possible to measure the states of a large power system interconnected with synchronized Phasor Measurement Units (PMU). This paper presents the idea of using remote signals obtained from PMU to damp SSR. An auxiliary subsynchronous damping controller (SSDC) has been proposed for a SVC, using the generator rotor speed deviation signal as the stabilizing signal to damp subsynchronous oscillations. Sturdiness of the controller has been examined by applying the disturbances in the system that causes significant changes in generator's operating point. The IEEE Second Benchmark (SBM) model is used for the analysis and the SVC is simulated using the Power System Block set (PSB) in the MATLAB/Simulink environment.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.