Abstract
Detecting interharmonics in power system for flicker troubshooting is highly desirable. Whereas these interharmonics are close to harmonic or fundamental component, it is always swamped by the main-lobe of harmonic nearby if the harmonic amplitude is much bigger than interharmonic amplitude, and vice versa. In this paper, a double-stage algorithm is proposed based on the windowed interpolation and the Prony method to overcome this problem. The interpolation method calculates most parts of harmonics and identifies the frequency interval in which two adjacent components are located, and then the Prony algorithm is used to compute these two adjacent components. Matlab simulation shows that two adjacent components can be detected with acceptable precision and the accuracy of other harmonic components enjoy the same as the interpolation algorithm.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.