Abstract

Series arc fault (SAF) poses a great challenge to the safe and stable operation of civil low-voltage distribution systems. For the accurate and rapid detection of SAF, this article proposes an SAF detection method using wavelet packet transform (WPT), residual convolution neural network (RCNN), and support vector machine (SVM). First, the raw current signal is decomposed into four wavelet components based on WPT. Then, the 1-D wavelet components are converted into 2-D matrices. Afterward, the matrices are input into RCNN through different channels. Finally, the detection results can be yielded by SVM. The effectiveness of the proposed method is verified based on offline experiments. The average detection accuracy of the proposed method is 99.72%, which is higher than that of the eight comparison methods. Moreover, the results of online experiments indicate that the detection time of the proposed method is less than 100 ms and can satisfy the requirement of standard 1699.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.