Abstract
The significant mutual-coupling impedances between the two circuits in double-circuit overhead-line construction are considered. The impedances measured by distance-protection relays are examined, both for stability for faults outside the protected zone and for operation for faults within the protected zone. This is done for different primary-system-circuit arrangements and for the condition where one circuit is out of service and earthed at both terminals. Some proposals for a practical setting policy are made.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Proceedings of the Institution of Electrical Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.