Abstract

Flashover tests were conducted at the Leadville EHV Test Facility of the Public Service Company of Colorado and Project EHV at Pittsfield, Mass., to obtain comparative data to evaluate the influence of air density on switching surge and impulse flashover strength of transmission line insulation. The tests showed that negative polarity flashover voltages are greater than those of positive polarity. Therefore, positive polarity will be the critical requirement for transmission line design for switching surge duty.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.