Abstract

The results of tests using a full-scale transmission line for the insulation design of the first 500-kV transmission line in Japan (the Boso Line of Tokyo Electric Power Company) are described. Having clarified the switching surge and impulse flashover characteristics of V-string insulator and strain insulator assemblies, installed on a simulated tower with a long gap of three meters or more, insulation was designed which withstands a switching surge of 2.5 per unit and is capable of unbalanced insulation between vertically arranged double circuits. The flashover path, predischarge, etc., of the switching surge was also investigated.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.