Abstract

Fault current magnitude and transient recovery voltage (TRV) are two important factors effecting circuit breaker (CB) operation during short-line faults. In this paper an inductive fault current limiter (FCL), which is a traditional kind of FCL, is modeled and simulated using electromagnetic transient program (EMTP) to study its effects on these two factors. It is assumed that the FCL is placed following the circuit breaker at the beginning of the line. Mathematical formulas are obtained for describing the relationship between the current limit factor and the recovery voltage of a CB as well as the rate of rise of recovery voltage (RRRV) based on theoretical analysis. The mathematical analysis is compared and verified with simulation results.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.