Abstract

Fault current limiter (FCL) is expected to ease the burden on circuit breakers by limiting the fault current to a desired level. However, the burden on the circuit breakers depends not only on the interrupting current but also on the rate of rise of recovery voltage (RRRV). Based on an equivalent model of the inductive FCL and with respect to FCL terminal fault and short-line fault respectively, strict mathematical formula are presented to describe the relationship between the RRRV and the current limit factor, the stray capacitance as well as the short-line fault distance. Further, detailed computations were carried out regarding a 220-kV transmission line with three-phase-to-ground faults to fully account for the concrete impacts on the RRRV from key influential factors. The calculation results by the proposed theoretical formula in this paper coincide well with the simulations in some previous publications. The specific investigation presents analytical basis and theoretical reference for optimal parameter design of inductive FCLs and reliable selection of the interrupting characteristics of HV circuit breakers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.