Abstract
Due to the nonlinear and unbalanced load of micro-grid, the output voltage quality on the main inverter side is easily affected in the micro-grid based on Master-Slave control.So, this paper put up a strategy that compensating the harmonic current and negative-sequence current by subordinate inverter. This strategy makes the current that flow through main inverter only have fundamental positive sequence component, so as to achieve the aim of improving the quality of the output voltage. Finally, the simulation model is built in the PSCAD simulation environment, which shows the effectiveness of the strategy.