Abstract

Experimental measurements were obtained to characterize the thermal performance of ducted air suction in conjunction with a pin-fin heat sink. Four single nozzles of different diameters and two multiple-nozzle arrays were studied at a fixed nozzle-to-target distance, for different turbulent Reynolds numbers 5000⩽Re⩽20,000. Variations of nozzle-to-target distance, i.e., open area, in ducted suction were found to have a strong effect on heat transfer especially with the larger diameter single nozzle and both multiple-nozzle arrays. Enhancement factors were computed with the heat sink in suction flow, relative to a bare surface, and were in the range of 8.3 to 17.7, with the largest value being obtained for the nine-nozzle array. Results from the present study on air jet suction are compared with previous experiments with air jet impingement on the pin-fin heat sink. Average heat transfer coefficients and thermal resistance values are reported for the heat sink as a function of Reynolds number, air flow rate, and pumping power. [S1043-7398(00)00903-8]