Abstract

In this paper an alternative method of connecting fixed-speed wind turbines with active pitch mechanisms or variable-slip generators is proposed and evaluated. Instead of using the conventional soft starter, external resistors are used. The method was evaluated via laboratory tests on a 15 kW machine, as well as theoretically on a 1 MW wind turbine. The proposed method causes smaller grid power quality impact, especially on inductive grids, compared with soft starters. This means that it will be possible to install constant-speed wind turbines to weaker grids utilizing this method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.