Abstract

The effects of the subcooling heat exchanger (SCHX) on the performance of the multi-split variable refrigerant flow (VRF) system with long pipe were investigated in a field test during the cooling season. By varying the refrigerant mass flow rate via the electronic expansion valve, the degree of subcooling was controlled. It was found that VRF system with SCHX improved the cooling performance factor (CPF) about 8.5% under similar outdoor temperature profiles, as compared to the baseline without SCHX. However, when the fraction of total refrigerant that passes through the SCHX was higher than 5.27%, the CPF starts to decrease due to the decreased refrigerant mass flow rate through the evaporators. Employing a SCHX in a VRF system with long pipe was found to be an effective method for improving the system performance and reliability.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.