Abstract
In this study, the performance of the VRF systems applying a bypass cycle and injection cycle using a sub-cooler is compared by numerical method. In the simulation for a multi-split variable refrigerant flow (VRF) system, it is important to predict the input power and mass flow rate of a scroll compressor with considering the refrigerant injection process in a compression chamber, and pressure drop and heat transfer in pipe lines between an outdoor unit and indoor units. Therefore, the simulation for a multi-split VRF system was developed with considering those, and validated with experimental data. The bypass and refrigerant injection have improvement potential to increase the cooling capacity due to increasing enthalpy difference in an evaporator. The refrigerant injection cycle has more improvement potential of performance than bypass cycle. Sub-cooling degree at inlet of EEV is above 10°C degree in two cycles, which can avoid flash gas generation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.