Abstract

Due to the low-damping characteristic of the voltage source converter based high voltage direct current (VSC-HVDC) transmission system, the line current will reach the peak value within a few milliseconds after DC fault, threatening the safety of power electronic devices. Therefore, a reliable and rapid protection scheme comprising fault identification and location is necessary. The detection time cost of traditional backup protections is high. Worse still, most existing methods cannot distinguish the double-pole-to-ground fault with unequal positive and negative pole fault resistances. To solve the issues, a backup protection based on the same/different-mode traveling wave, differential forward/backward current, and traveling waveform difference for VSC-HVDC lines is proposed in the paper. The fault characteristics of same/different-mode traveling wave and relationship between fault distance and differential forward/backward current are elaborated. The waveform differences in positive/negative-pole same/different-mode traveling waves and 1-mode differential forward/backward currents are summarized. According to these analyses, the protection is established and the VSC-HVDC is modeled in PSCAD. Based on the sufficient simulation tests, it is verified the proposed fault identification and location schemes have great performance, with superiority in fault resistance and distance tolerance (2,000 Ω and the whole line), strong anti-interference capability, fast fault distinguishment, and accurate fault location.