Abstract

In this study, the propane condensation heat transfer and pressure drop performance of a printed circuit heat exchanger was experimentally investigated. 30 experimental cases with different mass flux, saturation pressures and vapor quality were conducted. By analyzing these data, a heat transfer correlation similar to the Akers et al. correlation was presented [19]. The newly proposed correlation has a mean square percent error of 5.9% over the equivalent Reynolds number range from 690 to 5600. For the condensing pressure drop correlation, the Lockhart and Martinelli correlation showed the best performance [27].