Abstract

Condensation heat transfer and pressure drop of R170 were studied experimentally in a horizontal tube with inner diameter of 4 mm. The tests were conducted at saturation pressures from 1 MPa to 2.5 MPa, mass fluxes from 100 kg (m2∙s)−1 to 250 kg (m2∙s)−1 and average heat fluxes from 55.3 kW m−2 to 96.3 kW m−2 over the entire vapor quality range. The effects of vapor quality, mass flux and saturation pressure on condensation heat transfer and pressure drop were examined and analyzed. The experimental data were compared with various well-known correlations of condensation heat transfer coefficient and pressure drop. The comparison results showed that Koyama et al. correlation agreed with the experimental heat transfer coefficient with a mean absolute relative deviation less than 25%, and the Yan and Lin correlation can accurately predict the experimental pressure drop with a mean absolute relative deviation less than 18%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.