Abstract
GIS is the significant equipment in UHV network. However, after the UHV GIS busbar switch is opened, there will be a higher residual voltage on the GIS busbar, which causes the basin insulator flashover during the commissioning of the substation, which seriously affects the insulation and safety performance of the power system. It is very necessary to study the residual voltage on the GIS busbar. Therefore, we established a set of the GIS busbar residual voltage measurement system. Based on electric field measurement method, the GIS busbar residual voltage is measured in sulfur hexafluoride gas. The decay characteristics of the GIS busbar residual voltage under different polarity, different amplitude voltage and different temperature are studied. Research shows that the GIS busbar residual decays exponentially, and the decay of residual voltage is closely related to amplitude, temperature; at 26 °C and 0.4 MPa SF6 gas, the decay time of the GIS busbar residual voltage is as long as 22 hours after applying +450kV DC voltage, and the decay time constant is about 104 s order of magnitude.